Emerson 7ADTB Manuel de l'opérateur Page 1

Naviguer en ligne ou télécharger Manuel de l'opérateur pour Commutateurs de réseau Emerson 7ADTB. Emerson 7ADTB Operator`s manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 16
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
381333–140 D
50 Hanover Road, Florham Park, New Jersey 07932–1591 USA
For sales or service call 1 800 800–2726 (ASCO) www.ascopower.com
ASCO POWER TECHNOLOGIES CANADA PO Box 1238, 17 Airport Road, Brantford, Ontario, Canada N3T 5T3
Operator’s
Manual
7000 Seri es 7ADTB
Automatic Delayed–Transition Transfer
& Bypass–Isolation Switches
G design 1000 through 4000 amp. sizes
DANGER is used in this manual to warn of high
voltages capable of causin g shock , burns, or death.
WARNINGisusedinthismanualtowarn
of possible personal injury.
CAUTIONisusedinthismanualtowarn
of possible equipment damage.
4000 amp. size
Refer to the outline and wiring dra wings provided
with your 7000 Series ADTB for all installation and
connection details and accessories.
Refer to Group 5 Controller User’s Guide 381333–126
for ATS status display messages, time delays, pickup
& dropout settings, and adjustments.
An experienced licensed electrician must install the
7ADTB.
Rating Label
Each 7000 Series 7ADTB contains a rating label to
def in e th e load and fault circuit with stan d /c lo sin g
ratings. Refer to the label on the Transfer Switch for
spec if ic values.
Do not exceed the values on the rating label.
Exceeding the rating can cause personal injury
or serious equipment damage.
Namepl ate
The Transfer Switch nameplate includes data for
each specific 7000 Series 7ADTB Use the switch
only within the limits shown on this nameplate. A
typical Catalog Number is shown below with its
elements explained:
TABLE OF CONTENTS
section-page
INSTALLATION
Mounting 1-1.............................
Power Connections 1-2....................
Engine Starting & Auxiliary Circuits 1-2......
Functional Test 1-3, 1-4.....................
TESTING & SERVICE
Transfer Test & Preventive Maintenance 2-1..
Trouble-Shooting 2-2......................
BYPASSING & ISOLATING
Bypassing the ATS 3-1....................
Isolating the ATS 3-2......................
Return to Service 3-3, 3-4...................
INDEX back cover.........................
Vue de la page 0
1 2 3 4 5 6 ... 15 16

Résumé du contenu

Page 1 - Operator’s

381333–140 D50 Hanover Road, Florham Park, New Jersey 07932–1591 USAFor sales or service call 1 800 800–2726 (ASCO) www.ascopower.comASCO POWER TECHNO

Page 2

TESTING & SERVICE(continued)2-- 2TROUBLE-SHOOTINGNote any opt ional accessories that may be furnished onthe ADTB and review their operation. Refer

Page 3 - Phase Poles

SECTION 3 BYPASSING & ISOLATING3 --- 1BYPASSING THE ATS*This procedure explains how to Bypass the closedautomatic transfer switch contacts. Bypass

Page 4

BYPASSING & ISOLATING(continued)3 --- 2ISOLATING THE AT SIsolating is required before any service work can beperformed on the automatic transfer s

Page 5 - SECTION 1 INSTALLATION

BYPASSING & ISOLATING(continued)3 --- 3left support legright support leglocking pinwith clevis pinlocking pinwith clevis pinadjust length to touch

Page 6 - INSTALLATION (continued)

BYPASSING & ISOLATING(continued)3 --- 4RETURN TO SERVICEThis procedure explains how to return the automatictransfer switch (ATS) to service after

Page 7 - INSTALLATION

BYPASSING & ISOLATING(continued)3 --- 5RETURN TO SERVICE continued*This proc edu r e explain s how to retur n the Bypass Switc hHandletotheOPENpos

Page 8

INDEXPrinted in U.S.A. Copyright ASCO Power Technologies, L.P. 2009Aauxiliary circuits, 1–2Bbus connections, 1–2bypassing the ATS, 3–1Ccatalog number,

Page 10 - TESTING & SERVICE

Catalog Number IdentificationTypical 7000 Series ADTB catalog no. for overlappingneutral, 3 pole, 4000 amp., 480 V, in Type 1 enclosure:G7ADTB C 3 400

Page 12 - BYPASSING & ISOLATING

SECTION 1 INSTALLATION1 --- 1The ASCO 7000 Series Automatic Delayed–TransitionTra nsfer & Bypass–Isolati on S witch (ADTB) consistsof an upper byp

Page 13

INSTALLATION (continued)1 --- 2De–energize the conductors before making anyline or auxiliary circuitry connections. Be surethat Normal and Emergency l

Page 14

INSTALLATION(continued)1 --- 3REDREDGREENGREENobservethese lightsAMBERFigure 1-3. Standard controls and indicators.Functional TestRead all instruction

Page 15

INSTALLATION (continued)1 --- 4REDREDGREENGREENobservethese lightsAMBERoperatethis switchFigure 1-4. Standard controls and indicators.2 – Electrical O

Page 16

SECTION 2 TESTING & SERVICE2-- 1TRANSFER TESTTest the Automatic Delayed–Transition Transfer Switchportion of the 7000 Series ADTB at least once am

Commentaires sur ces manuels

Pas de commentaire