MODEL 5081-C SECTION 2.0
INSTALLATION
2.5 POw ER SUPPLy w IRING FOR
MODEL 5081-C-FF
2.5.1 Power Supply w iring. Refer to Figure 2-5 and
Figure 2-6.
Run the power/signal wiring through the opening nearest
terminals 15 and 16. u se shielded cable and ground the
shield at the power supply. To ground the transmitter,
attach the shield to the grounding screw on the inside of
the transmitter case. A third wire can also be used to con-
nect the transmitter case to earth ground.
NOTE
For optimum EMi/RFi immunity, the power sup-
ply/output cable should be shielded and
enclosed in an earth-grounded metal conduit.
d o not run power supply/signal wiring in the same con-
duit or cable tray with AC power lines or with relay actu-
ated signal cables. Keep power supply/signal wiring at
least 6 ft (2 m) away from heavy electrical equipment.
FIGURE 2-5. Typical Fieldbus Network Electrical
w iring Configuration
FIGURE 2-6. Model 5081-C-FF Power w iring Details
5081-C pH/o RP
Transmitter
5081-C pH/o RP
Transmitter
9 - 32