Reference Manual
00809-0200-4728, Rev RA
Section 6: Troubleshooting
April 2015
Troubleshooting
6.4.3 Other LCD display messages
Calibration Error
[none] [none]
The value entered for the
user trim point was not
acceptable.
1. Re-trim the device, make sure the user
entered calibration points are close to
the applied calibration temperature.
Sensor Out of
Operating
Limits
(1)
SAT
SNSR 1
XX.XXX
°C
SAT
SNSR 1
XX.XXX
°C
Sensor # readings are
outside the sensor's
specified range.
1. Verify the process temperature is
within the specified sensor's range.
Use the Sensor Information button to
compare with the process
temperature.
2. Verify the sensor is properly wired and
connected to the terminals.
3. Verify the integrity of the sensor and
sensor lead wires. If the sensor is
faulty, repair or replace the sensor.
Terminal
Temperature
Out of
Operating Limits
SAT
TERM
DEGRA
WARN
SAT
TERM
DEGRA
WARN
The Terminal Temperature
is outside the on-board RTD
specified operating range
1. Verify the ambient temperature is
within the device specified operating
range using the Terminal Temperature
Information Button.
(1) Sensor 1 is used here as an example. If Dual Sensors are ordered this alert can apply to either sensor.
Alert name LCD screen LOI screen Problem Recommended action
LCD is not
displaying
correctly or at all
644
HART 7
644
HART 7
The display may not be
functioning or it may be
stuck on Home screen
If the meter does not appear to
function, make sure the transmitter is
configured for the meter option you
desire. The meter will not function if the
LCD Display option is set to Not Used.
Analog Output
Fixed
WARN
LOOP
WARN
FIXED
WARN
LOOP
WARN
FIXED
The analog output is set to a
fixed value and is not
currently tracking the HART
Primary Variable.
1. Verify that it was intended for the
transmitter to be operating in “Fixed
Current Mode.”
2. Disable “Fixed Current Mode” in
Service Tools to have the analog
output operate normally.
Simulation Active
[none] [none]
The device is in simulation
mode and may not be
reporting actual
information.
1. Verify simulation is no longer
required.
2. Disable simulation mode in service
tools.
3. Perform a device reset.
Alert name LCD screen LOI screen Problem Recommended action