61
Rosemount 3051
September 2014
www.rosemount.com
limitation-Selection, installation and maintenance”
GB15577-2007 “Safety regulations for dust explosion
prevention and protection”
N3 China Type n
Certificate: GYJ101111X
Standards: GB3836.1-2000, GB3836.8-2003
Markings: Ex nA IIC T5 (-40°C
Ta +70°C)
Special Conditions for Safe Use (X):
1. Symbol “X” is used to denote specific conditions of use:
The apparatus is not capable of withstanding the 500V test
to earth for one minute. The must be taken into
consideration during installation.
2. The ambient temperature range is -40°C
Ta +70°C.
3. Maximum input voltage: 55V.
4. Cable glands, conduit or blanking plugs, certified by NEPSI
with Ex e or Ex n protection type and IP66 degree of
protection provided by enclosure, should be used on
external connections and redundant cable entries.
5. Maintenance should be done in non-hazardous location.
6. End users are not permitted to change any internal
components but to settle the problem in conjunction with
manufacturer to avoid damage to the product.
7. During installation, use and maintenance of this product,
observe the following standards:
GB3836.13-1997 “Electrical apparatus for explosive gas
atmospheres Part 13: Repair and overhaul for apparatus
used in explosive gas atmospheres”
GB3836.15-2000 “Electrical apparatus for explosive gas
atmospheres Part 15: Electrical installations in hazardous
area (other than mines)”
GB3836.16-2006 “Electrical apparatus for explosive gas
atmospheres Part 16: Inspection and maintenance of
electrical installation (other than mines)”
GB50257-1996 “Code for construction and acceptance of
electric device for explosion atmospheres and fire hazard
electrical equipment installation engineering”
Japan
E4 Japan Flameproof
Certificate: TC20577, TC20578, TC20583, TC20584
[HART]; TC20579, TC20580, TC20581,
TC20582 [Fieldbus]
Markings: Ex d IIC T5
Technical Regulations Customs Union
(EAC)
EM, IM, KM Contact an Emerson Process Management
representative for further information.
Combinations
K2 Combination of E2 and I2
K5 Combination of E5 and I5
K6 Combination of C6, E8, and I1
K7 Combination of E7, I7, and N7
K8 combination of E8, I1, and N1
KB Combination of E5, I5, and C6
KD Combination of E8, I1, E5, I5, and C6
Conduit Plugs and Adapters
IECEx Flameproof and Increased Safety
Certificate: IECEx FMG 13.0032X
Standards: IEC60079-0:2011, IEC60079-1:2007,
IEC60079-7:2006-2007
Markings: Ex de IIC Gb
ATEX Flameproof and Increased Safety
Certificate: FM13ATEX0076X
Standards: EN60079-0:2012, EN60079-1:2007,
IEC60079-7:2007
Markings: II 2 G Ex de IIC Gb
Conduit Plug Thread Sizes
Thread Identification mark
M20 x 1.5 M20
1/2 - 14 NPT 1/2 NPT
G1/2A G1/2