NetSure™ ITM with eSure™ Technology
Installation Manual, Section 6040 (Issue AB, April 8, 2013)
Spec. No: 582145500
65
Section 6040
Model: NetSure™ ITM Issue AB, April 8, 2013
7.5.6 Advanced Control Unit Plus (ACU+) Controller
7.5.7 SM-DU+
Display LCD with 4 × 16 Characters
Communication RS232, RS485, Ethernet, USB
Protocol HTTP, SNMP, EEM, SocTpe, RSoc
Local Indicators Green LED: Illuminates when CPU is working
correctly.
Red LED: Illuminates when there is a critical or
warning alarm.
Yellow LED: Illuminates when there is an
information alarm.
Inputs
5 Analog Inputs
14 Digital Inputs
Outputs
1 Output
System Output Voltage
Battery Voltage
Battery Temperature
Ambient Temperature
Battery Shunt (for Battery Current)
3 Battery Fuses
2 DC Distribution Fuses
8 Generic Digital Inputs (where D15 reserved for
"Fan CB Tripped" and D16 for "Fan Alarm")
1 Contactor Status
Contactor Control
DC Power Plant Alarms AC Mains Failure, PCU Failure, High Voltage
Shutdown, Fan Failure, Thermal Derating (of PCU
output due to high temperature)
Monitoring Capability SNMP/Web Based Monitoring Included;
Compatibility with SiteScan Available
EnergyMaster Remote Monitoring (contact your
Emerson Representative)
Communication RS485, CAN, RS232
Local Indicators Green LED: Illuminates when CPU is working
correctly. Flashes (1/3Hz) to indicate
communication fault with controller. Flashes (1Hz)
to indicate communicating with controller.
Red LED: Illuminates when there is a critical or
warning alarm.
Yellow LED: Illuminates when there is an
information alarm.
Inputs 22 Current Measurements
22 DC Fuse/Breaker Status Detection