Page 1 - & GXT 10

POWER AVAILABILITYMAINTENANCE BYPASS CABINET FOR NFINITY™& GXT 10KVAUSER MANUAL

Page 2 -

General Description6Figure 3 Rear view (with transformer)Hardwire outputterminal block (TB6)Configurable output distribution (optional)Hardwire output

Page 3 - TABLE OF CONTENTS

Modes of Operation72.0 MODES OF OPERATIONThe Nfinity Maintenance Bypass Cabinet is designed to operate in two modes: UPS Mode and Bypass Mode.2.1 UPS

Page 4

Major Components83.0 MAJOR COMPONENTSThe following is a general description of each component and its functions. Please review this section carefully,

Page 5 - SAVE THESE INSTRUCTIONS

Preparation94.0 PREPARATIONThese installation instructions provide all the information needed for positioning the Nfinity Mainte-nance Bypass Cabinet

Page 6 - GLOSSARY OF SYMBOLS

Unloading105.0 UNLOADINGThe unit frame is bolted to the shipping pallet to ensure safety. Liebert recommends using a pallet jack to transport the unit

Page 7 - 1.0 GENERAL DESCRIPTION

Unloading115.2 Stationary MountingAdditional stability can be added by bolting the mounting brackets (used in shipping) to the floor.For greater stabi

Page 8 - Figure 1 Front view

Cable Installation126.0 CABLE INSTALLATION6.1 Wiring PreparationBe sure that the unit is not connected to any AC mains power source or UPS before inst

Page 9

Cable Installation13Figure 7 Maintenance Bypass Cabinet with transformerFigure 8 Maintenance Bypass Cabinet without transformerSW2UPS Input SwitchTran

Page 10

Cable Installation146.4 Removing the Cover PlatesOn the back of the Maintenance Bypass Cabinet, cover plates are over the input and output terminals (

Page 11 - 2.0 MODES OF OPERATION

Cable Installation156.7 Input and Output WiringTo connect the input wiring:1. Locate the input wiring access (see illustration at right).2. Remove the

Page 13 - 4.0 PREPARATION

Cable Installation16Figure 9 Electrical connections—transformer model MBC 120V120V208V240VCommon GroundWire Connection Torque Value: 13 in-lbsCommon G

Page 14 - 5.0 UNLOADING

Cable Installation17Figure 10 Electrical connections—non-transformer model MBC120V120V208V240VCommon GroundWire Connection Torque Value: 13 in-lbsComm

Page 15 - 5.2 Stationary Mounting

Cable Installation18Figure 11 Connecting Nfinity to Maintenance Bypass with transformerNOTE1. SINGLE-SOURCE FEED—If feeding the Maintenance Bypass Cab

Page 16 - 6.0 CABLE INSTALLATION

Cable Installation19Figure 12 Connecting Nfinity to Maintenance Bypass without transformer NOTE1. SINGLE-SOURCE FEED—If feeding the Maintenance Bypass

Page 17

Cable Installation20Figure 13 Connecting Maintenance Bypass to GXT10000T-208X!CAUTIONIt is mandatory to connect exactly as shown.NOTE1. SINGLE-SOURCE

Page 18 - 6.5 Power Cable Installation

Cable Installation21Figure 14 Connecting Maintenance Bypass to GXT10000T-240XNOTE1. SINGLE-SOURCE FEED—If feeding the Maintenance Bypass Cabinet from

Page 19 - 6.7 Input and Output Wiring

Operation227.0 OPERATION7.1 Start-Up and InitializationTo start up the Nfinity UPS while it is connected to the Nfinity Maintenance Bypass:1. Set the

Page 20

Maintenance238.0 MAINTENANCE8.1 Proper CareKeeping your Liebert Nfinity Maintenance Bypass Cabinet operating properly is imperative to opti-mal perfor

Page 21

Specifications249.0 SPECIFICATIONSGeneral & EnvironmentalRatingUnit RatingkVAModels NMB1x and NMB4x = 18Models NMB5x and NMB8x = 20AmpsModels NMB1

Page 22 - TRANSFORMER

Specifications25NOTES

Page 23 - WITHOUT TRANSFORMER

iTABLE OF CONTENTSIMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1GLOSSA

Page 24 - RANSFORMER

Specifications26

Page 26 - 7.0 OPERATION

The Company Behind the ProductsWith over a million installations around the globe,Liebert is the world leader in computer protectionsystems. Since its

Page 27 - 8.0 MAINTENANCE

ii8.0 MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .238.1 Proper Care.

Page 28 - 9.0 SPECIFICATIONS

1IMPORTANT SAFETY INSTRUCTIONSSAVE THESE INSTRUCTIONSThis manual contains important instructions that should be closely followed during installation a

Page 29 - Specifications

2GLOSSARY OF SYMBOLSRisk of Electrical ShockIndicates Warning or Caution Followed by Important InstructionsAC InputAC OutputRequests the user to consu

Page 30

General Description31.0 GENERAL DESCRIPTIONCongratulations on your purchase of Liebert’s Nfinity™ Maintenance Bypass Cabinet with Config-urable Output

Page 31

General Description4Figure 1 Front viewBypass availabilityindicator (amber)Cooling fans(transformer models only)UPS input power present (amber)UPS out

Page 32

General Description5Figure 2 Rear view (without transformer)Configurable outputdistribution (optional)Hardwire output (standard)Maintenance bypass inp