Chapter 4 Alarm Handling 11
NetSure 211 C23 Embedded Power Supply System User Manual
No.
Alarm
Handling method
7
LVD2
1. Check if there is a mains failure, and the battery voltage is lower than the ‘BLVD’ value, or the battery
discharge time is more than the ‘BLVD Time’.
2. Check if someone manually disconnected the battery from the system
8
Rect Failure
The red indicator on the rectifier will turn on.
1. Reset the rectifier by powering it off and then on again.
2. If the alarm persists, replace the rectifier
9
Rect Protect
Check if the mains voltage is outside the range of 80V (AC under-voltage point) ~ 295V (AC over-voltage
point).
If the power supply is often outside this range, consult with the power grid maintenance personnel to
improve it
10
Rect Fan Fails
1. Check whether the rectifier fan is still working.
2. If the fan stands still, check whether the fan is blocked or not. If yes, clean it; if not, or if the fault
persists after the fan is cleaned, replace it (see 4.2 Handling Rectifier Fault)
11
Rect Not Respond
Check if the communication between rectifier and monitoring module failed. If the communication is
normal, restart the rectifier by pulling it out and pushing back in. If the alarm persists, replace the rectifier
12
Batt Over Temp
1. Check if there is a battery internal fault. If yes, replace the battery.
2. Check if the battery room temperature is too high. If yes, cool down the battery room
4.2 Handling Rectifier Fault
Handling indicator fault
The symptoms of usual rectifier faults include: green indicator (run indicator) off, yellow indicator (protection indicator)
on, yellow indicator blink, red indicator (fault indicator) on and red indicator blink.
The indicators are shown in Figure 4-1 and handling methods of the rectifier faults are given in Table 4-2.
R48-1000
Run indicator
Protection indicator
Fault indicator
Figure 4-1 Rectifier indicator
Table 4-2 Handling methods of the rectifier faults
Symptom
Monitoring
module alarms
Causes
Handling methods
Run indicator off
No alarm
No input/output voltage
Make sure there is input/output voltage
Assistant power source of the rectifier fails
Change the position of the faulty module with
normal module. If the faulty module cannot
work normally, replace it
Run indicator
blinks
No alarm
The monitoring module performs operations
upon the rectifier
Yellow
indicator on
Rect over temp
AC input voltage abnormal
Make sure the AC input voltage is normal
Over-
temperature
protection due
to:
Fan blocked
Remove the object that blocks the fan
Ventilation path blocked at
the inlet or vent
Remove the object at the inlet or vent
Ambient temperature too
high or the inlet too close to
a heat source
Decrease the ambient temperature or remove
the heat source