Installation
2
Figure 1 Typical cabinet and floor planning dimension data
RDC11014
Rev. 0
FRONT & REAR VIEW RIGHT SIDE VIEW
TOP VIEW
24"
(610mm)
24"
(610mm)
1.5"
(38mm)
21"
(533mm)
14"
(356mm)
5"
(127mm)
CLEARANCE HOLE
0.344" (8.74mm)
RECOMMENDED
CLEARANCE OF
18" (457mm)
ABOVE UNIT
FOR COOLING
AIR FLOW
RECOMMENDED
MINIMUM CLEARANCE
OF 36" (914mm) AT
FRONT, REAR AND
RIGHT SIDE FOR
SERVICE ACCESS
NOTES:
1. WEIGHT: 750 LB. (340kg)
2. HEAT OUTPUT: 3,412 BTU/HR (1kW)
120° DOOR SWING
120° DOOR SWING
23.7"
(602mm)
23.7"
(602mm)
FOOTPRINT
REMOVE ONE 24" X 24"
FLOOR TILE FOR INPUT/OUTPUT
CABLE ACCESS
25.5"
(648mm)
24"
(610mm)
28.6" (726mm)
OVERALL
DIMENSION
23.7"
(602mm)
78"
(1981mm)
24"
(610mm)
PROJECTION OF BEZELS
(FRONT & REAR)
0.63" (16mm)