System Application Guide SAG584000300
NetSure 4015 30kW 400V DC Power System Issue AB, April 5, 2013
Spec. No. 584000300 (Model 4015-X003)
Page 21 of 32
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Home
RECOMMENDED WIRING SIZES, BRANCH
CIRCUIT PROTECTION, AND CRIMP LUGS
Equipment Grounding
For equipment grounding requirements, refer to the current edition of the American National Standards
Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code (NEC),
applicable local codes, and your specific site requirements. For operation in countries where the NEC is not
recognized, follow applicable codes.
Factory Furnished IT Rack Frame Grounding
When the system is pre-assembled and pre-wired in a factory furnished IT rack (List R1, R2), grounding leads
are factory wired from the individual system sub-racks to a ground bar located on the rear left side of the
furnished IT rack. Customer is required to run a grounding cable from this ground bar to site ground. Refer to
Table 4 for recommended grounding wire size and lug selection.
Factory Furnished IT Rack Frame Grounding
(Grounding Studs for Lug Connection Provided)
Recommended
Wire Size
Lug Requirements
Recommended Lug
(Emerson P/N)
8 AWG
(10mm
2
)
2-Hole,
1/4" Bolt Clearance Holes,
5/8" Centers
245390200
Table 4
Recommended Factory Furnished IT Rack Frame Grounding Wire Size and Lug
Sub-Rack Frame Grounding (for systems installed in a customer furnished IT rack)
When system components are provided individually to be installed in a customer furnished IT rack, the
individual sub-racks must be grounded on site by the customer.
A grounding stud is located on the rear of the power and control sub-rack and distribution sub-rack. A
grounding stud is located on the rear side panel of the battery tray.
Refer to Table 5 for recommended grounding wire size and lug selection. For convenience, grounding cables
are furnished loose with each sub-rack as shown in Table 5. These cables are assembled with the 2-hole lug
listed in Table 4 on one end and the 1-hole lug listed in Table 5 on the other end.
Sub-Rack Frame Grounding
(Grounding Stud for Lug Connection Provided)
Recommended
Wire Size
Lug Requirements
Recommended Lug
(Emerson P/N)
Furnished Grounding Cable
8 AWG
(10mm
2
)
1-Hole,
1/4 Bolt
Clearance Hole
245359690
Power and Control Sub-Rack:
P/N 554932, 584mm (23”).
Load Distribution Sub-Rack:
P/N 554931, 864mm (34”).
Battery Tray:
P/N 554934, 1575mm (62”).
Table 5
Recommended Sub-Rack Frame Grounding Wire Size and Lug